Skip to main content

AvCount Lite Particle Counter - SA1800-2


Petroleum and Fuel Analysis

Provides reliable results for determining the size and distribution of particles

The AvCount Lite portable automatic particle counter provides reliable results for determining the size and distribution of particles in light and middle distillate fuels, including aviation fuel and kerosene, biodiesel, low viscosity oils and hydraulic oils.

The particle counters simple operation makes testing bottle samples or on-line quick and easy, with results in under 3 minutes.

System Description

The AvCount Lite displays the cumulative, particles/ml and ISO 4406 cleanliness codes. Up to 600 measurements can be saved to the internal memory, downloaded to a PC/laptop or printed via the internal printer.

Supplied with: sample bottles, sample probe, waste pipe, universal voltage power supply, USB cable, calibration certificate and a USB memory stick containing handbooks and Partikel software for basic test method programming and data download.

  • ● ISO 11171 calibration

  • ●  Cumulative Particles/ml

  • ● ISO 4406 Cleanliness Codes

  • ● Portable, compact instrument

  • ● Online/offline (bottle sample)

  • ● Stand-alone or PC controlled

  • ● Programmable via PC

  • ● Integrated printer

  • ● Battery power optional

Product Specialist

Mikael Alfredsson Kovalent

Mikael Alfredsson

"Our expert in Digestion, Extraction, Syntesis and Evaporation with more than 20 years experience in the field of sales and service. Contact me for if you have questions or need a quotation"

Additional Information

Sample viscosity:
The AvCount Lite can analyse samples with kinematic viscosities of up to 64 mm2/s. When used in conjunction with the optional Sample Delivery System, the viscosity range is extended up to 200 mm/s.

Precision and accuracy:
AvCount Lite is fitted with a precision dual piston pump. When measuring samples from a bottle, the pump draws an aliqot of sample through the measurement cell at a consistent flow rate. When connected to a pressurised line, the pump provides accurate metering and control.

Protrend Software:
Optional Protrend Software SA1810-0 can be purchased to control an AvCount Lite from a personal computer or laptop. Local custom test methods can be created, tests run and data downloaded. Protrend supports multiple AvCount Lite units, synchronising the sampling and measurement to allow trend analysis.

Calibration and verification:
AvCount Lite utilises 16 point calibration. Calibration can be carried out either using NIST traceable standard solutions or by interfacing with a primary calibrated ‘Master’ AvCount Lite. Calibration can be carried out at a user site or at our authorised regional laboratories. Seta authorised training is required to perform a calibration. Verification can be performed using AvCount Verification Material.

Industries

  • ● Aviation

  • ● Biodiesel

  • ● Lubricants

  • ● Petroleum - Fuels and Oils

Methods

  • ● ASTM D975

  • ● ASTM D7619

  • ● IP 565

  • ● IP 630

  • ● CEN/TR 15367-1

  • ● CEN/TR 17548

  • ● DEF STAN 91-091

  • ● DEF STAN 91-86

  • ● IEC 60970

  • ● ISO 4406

  • ● JIS B 9932:2012

  • ● JIS B 9933:2021

  • ● JIS B 9934:2012